ODM Rcd Breaker Factories – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn Detail:
Feature
Zinc oxide without spark gap with synthetic cover.
•Varistors have the ability to instantly switch from an insulating state to a conductive state in the event of an overvoltage,
•The composite structure in fiberglass impregnated with epoxy resin ensures the mechanical strength of the stack,
•The outer silicone elastomer shell provides dielectric strength.
Reference standards:IEC 60099-4 – 10 kA,20kA / class 2~4, IEC 60815 – pollution level IV
Performance
Nominal discharge current:10 kA (8/20 wave)
Large amplitude current:100 kA (wave 4/10)
Rated voltage:from 60kV to 216 kV
Creepage line:> 31 mm / kV
(level IV according to IEC 60815)
Energy capacity(mim):4.8 kJ / kV from Uc (wave 4/10)
Long time current(min):600 A (wave 2 ms)
Resistance to short-circuit currents: 31.5 kA / 0.2 s – 600 A / 1 s
•High flow power,
•Lowering of the residual voltage level,
•Minimal Joule losses,
•Stability of characteristics over time
•Simple installation,
•Maintenance free.
Installation conditions
•For indoors and outdoors;
•Ambient air temperature :-40℃~+45℃
•Maximum solar radiation not exceeding 1.1kW/m2;
•Altitude not exceeding 3000m;
•Rated frequency for a.c. system : 48Hz~62Hz;
•Maximum wind velocity not over 40m/s;
•Earthquake intensity not exceeding 8 degree;
•Power-frequency voltage applied continuously between the terminals of the arrester not over exceeding its continuous operating voltage;
Parameters data
Rated voltage |
kV |
60 |
72 |
84 |
96 |
108 |
120 |
132 |
144 |
168 |
192 |
204 |
216 |
Continuous operating voltage |
kV |
48 |
58 |
67.2 |
75 |
84 |
98 |
106 |
115 |
131 |
152 |
160 |
168 |
Maximum residual voltage at 5 kA 8/20µs |
kV peak |
148.6 |
178.3 |
208.0 |
237.8 |
262.4 |
291.6 |
320.8 |
349.9 |
408.2 |
466.6 |
495.7 |
524.9 |
Maximum residual voltage at 10 kA 8/20µs |
kV peak |
154.8 |
185.8 |
216.7 |
247.7 |
272.2 |
302.4 |
332.6 |
362.9 |
423.4 |
483.8 |
514.1 |
544.3 |
Maximum residual voltage at 20 kA 8/20µs |
kV peak |
166.6 |
199.9 |
233.2 |
266.6 |
291.6 |
324.0 |
356.4 |
388.8 |
453.6 |
518.4 |
550.8 |
583.2 |
Switching residual voltage at 500A – 30/80µs |
kV peak |
117.9 |
141.5 |
165.1 |
188.6 |
212.2 |
235.8 |
259.4 |
283.0 |
330.1 |
377.3 |
400.9 |
424.4 |
Steep current impulse residual voltage at 10kA – 1/2,5µs |
kV peak |
166.5 |
199.8 |
233.1 |
266.4 |
299.7 |
333.0 |
366.3 |
399.6 |
466.2 |
532.8 |
566.1 |
599.4 |
Device dimensions
10kA |
60kV |
72kV |
84kV |
96kV |
108kV |
120kV |
132kV |
144kV |
168kV |
192kV |
204kV |
216kV |
A |
90 |
112 |
||||||||||
B |
210 |
232 |
||||||||||
C |
174 |
196 |
||||||||||
H |
Customized according to customer requirements |
|||||||||||
Creepage distance (mm) |
Customized according to customer requirements |
(All dimensions in mm.)
Product detail pictures:
Related Product Guide:
We also offer you product sourcing and flight consolidation expert services. We've our personal manufacturing unit and sourcing business. We can offer you virtually every variety of merchandise associated to our item range for ODM Rcd Breaker Factories – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn , The product will supply to all over the world, such as: Iraq, Leicester, Sao Paulo, We always stick to the tenet of "sincerity, high quality, high efficiency, innovation". With years of efforts, we have established friendly and stable business relationships with worldwide customers. We welcome any of your inquiries and concerns for our products, and we are sure that we will offer just what you want, as we always believe that your satisfaction is our success.