ODM Extension Sockets Suppliers – Supply China Nt-500 Liquid Nitrogen Generators Nitrogen Gas Generator Machine Filling Machine Nitrogen – Jonchn Detail:
Summary
1.1Product features
RT16 pole contact fuse (hereinafter refened to as fuse) is in accordance with GB / T13539.2 standard, and has obtained “China National Compulsory Product Certification” (i.e. passed “CCC” certification).
1.2Main purpose
The fuse is suitable for line overload and short-circuit protection in the distribution equipment of industrial electrical equipment with AC rated frequency of 50Hz, rated voltage of AC to 690V, DC 250V to 440V and rated cunent to 1250A.
1.3Type and specification
Fuse is divided into six sizes according to the size of fuse tube. Each size has conesponding rated current range. Refer to main technical parameters for rated cun ent level of fuse of various sizes. The fuse can be equipped with an impactor according to the user’s requirements, and the impactor is generally located directly above the fuse contact.
1.4Nomenclature of fuses
“”I— Impactor: “None” (can be omitted), “A” means yes
Rated current of fuse link (a),
Fuse size: 000, 00, 1, 2, 3, 4
Design code (knife type contact)
Packed closed tube fuse
1.5Normal working conditions
1.5.1Ambient air temperature
The ambient air temperature shall not exceed 40 °C, the average value measured in 24 hours shall not exceed 35 C, and the average value measured in one year shall be lower than this value.
The minimum ambient air temperature is – 5 C.
1.5.2Altitude
The altitude of the installation site shall not exceed 2000m.
1.5.3Atmospheric conditions
Its relative humidity shall not exceed 50% at the maximum temperature of 40 °C
A higher relative humidity can be obtained at a lower temperature, for example, up to 90% at 20 C.
Under these conditions, moderate condensation may occur by chance due to temperature changes. Without consultation with the manufacturer, the fuse cannot be installed in the place with salt mist or abnormal industrial deposit.
1.5.4Voltage
The maximum system voltage shall not exceed 110% of the rated fuse voltage.
For fuse with rated voltage of 690V AC and 250V / 440V DC, the maximum system voltage shall not exceed 105% of rated voltage of fuse.
1.6Normal installation conditions
1.6.1Installation category
The installation categoiy of fuse is class III.
1.6.2Pollution level
The anti pollution degree of fuse shall not be lower than level 3.
1.6.3Installation mode
The fuse can be installed vertically, horizontally or obliquely in the workplace without significant shaking and impact vibration.
1.7Breaking range and use category
The fuse link for fuse is a fuse link with general purpose and full range breaking capacity, i.e. “gG” fuse link.
Summary
1.1Product features
RT16 pole contact fuse (hereinafter refened to as fuse) is in accordance with GB / T13539.2 standard, and has obtained “China National Compulsory Product Certification” (i.e. passed “CCC” certification).
1.2Main purpose
The fuse is suitable for line overload and short-circuit protection in the distribution equipment of industrial electrical equipment with AC rated frequency of 50Hz, rated voltage of AC to 690V, DC 250V to 440V and rated cunent to 1250A.
1.3Type and specification
Fuse is divided into six sizes according to the size of fuse tube. Each size has conesponding rated current range. Refer to main technical parameters for rated cun ent level of fuse of various sizes. The fuse can be equipped with an impactor according to the user’s requirements, and the impactor is generally located directly above the fuse contact.
1.4Nomenclature of fuses
“”I— Impactor: “None” (can be omitted), “A” means yes
Rated current of fuse link (a),
Fuse size: 000, 00, 1, 2, 3, 4
Design code (knife type contact)
Packed closed tube fuse
1.5Normal working conditions
1.5.1Ambient air temperature
The ambient air temperature shall not exceed 40 °C, the average value measured in 24 hours shall not exceed 35 C, and the average value measured in one year shall be lower than this value.
The minimum ambient air temperature is – 5 C.
1.5.2Altitude
The altitude of the installation site shall not exceed 2000m.
1.5.3Atmospheric conditions
Its relative humidity shall not exceed 50% at the maximum temperature of 40 °C
A higher relative humidity can be obtained at a lower temperature, for example, up to 90% at 20 C.
Under these conditions, moderate condensation may occur by chance due to temperature changes. Without consultation with the manufacturer, the fuse cannot be installed in the place with salt mist or abnormal industrial deposit.
1.5.4Voltage
The maximum system voltage shall not exceed 110% of the rated fuse voltage.
For fuse with rated voltage of 690V AC and 250V / 440V DC, the maximum system voltage shall not exceed 105% of rated voltage of fuse.
1.6Normal installation conditions
1.6.1Installation category
The installation categoiy of fuse is class III.
1.6.2Pollution level
The anti pollution degree of fuse shall not be lower than level 3.
1.6.3Installation mode
The fuse can be installed vertically, horizontally or obliquely in the workplace without significant shaking and impact vibration.
1.7Breaking range and use category
The fuse link for fuse is a fuse link with general purpose and full range breaking capacity, i.e. “gG” fuse link.
2.Structural features and working principle
The fuse consists of fuse base and fuse link. The fuse base is composed of base contact, base plate, etc. The fuse link is composed of fuse tube, melt, quartz sand, knife type contact, etc.
When the fuse is installed in the circuit, when the current passing tlirough the fuse exceeds a certain value for a sufficient time, the melt in the fuse body will be fused, and the arc generated when the fuse is fused by quartz sand in the fuse tube will be extinguished, so as to achieve the purpose of breaking the circuit.
When the melt is blown, the indicator on the fuse link will pop up, indicating that the fuse link is blown.
For the fuse equipped with an impactor, when the melt is fused, the impactor will pop out automatically. The user only needs to install a microswitch or a suitable signal sending device (selected and purchased by the user) in front of the impactor, and then the required signal can be obtained after the fuse is fused.
3.Main technical parameters
Main technical parameters of fuse are shown in Table 1
Model |
Rated voltage V |
Rated current A |
Rated breaking capacity |
Rated power w |
|||||
Base |
Fuse link |
AC500V |
AC690V |
DC |
Rated withstand impulse voltage of base |
Rated power of base |
Rated dissipation power of fuse link |
||
RT16-000 | DC250AC500AC690 | 160 | 2, 4, 6, 8, 10, 12, 16, 20, 25,32, 40, 50, 63, 80, 100 | 120kA |
50kA |
250V100KA | >12 | <12 | |
RT16-00 | 160 | 2, 4, 6, 8, 10, 12, 16, 20, 25, 32,40, 50, 63, 80, 100, 125,160 |
120kA |
50kA |
250V100KA | ||||
RT16-1 | 250 | 80, 100, 125, 160, 200, 224,250 |
120kA |
50kA |
440V100KA |
6kV |
>32 |
W32 | |
RT16-2 | DC440AC500AC690 | 400 | 125, 160, 200, 224, 250,315, 355,400 |
120kA |
50kA |
440V50KA |
N45 |
<45 | |
RT16-3 | 630 | 315, 355, 400, 500, 630 |
120kA |
50kA |
440V50KA |
>60 |
W60 | ||
RT16-4 | DC250AC500 | 1250 | 800、 1000、 1250 |
lOOkA |
— | 250V50KA |
3110 |
WHO |
4. Outline, installation dimension and weight of fuse
4.1 Outline, installation dimension and weight of fuse base
See Figure 1 and table 2 for the outline and installation dimension of fuse base, and see Table 2 for the weight of fuse base.
Model |
A |
B |
c |
D |
E |
F |
RT16-00 |
102 |
122 |
60 |
82 |
25 |
— |
RT16-1 |
173 |
197 |
83 |
96 |
25 |
28 |
RT16-2 |
199 |
223 |
96 |
116 |
26 |
28 |
RT16-3 |
208 |
248 |
104 |
125 |
26 |
28 |
RT16-4 |
260 |
300 |
135 |
165 |
30 |
44 |
Table 2 (Continued)
Model |
G |
H |
I |
M |
Weight(kg) |
RT16-00 |
8 |
25 |
30 |
M8 |
0. 20 |
RT16-1 |
11 |
26 |
55 |
MIO |
0. 55 |
RT16-2 |
11 |
30 |
61 |
MIO |
0. 84 |
RT16-3 |
11 |
39 |
61 |
M12 |
0. 98 |
RT16-4 |
13 |
45 |
93 |
M16 |
3. 09 |
4.2 Boundary dimension and weight of fuse link
Table 3 boundary dimension and weight of fuse link
Model | a | b | C | d | e | Weight (kg) |
RT16-000 | 49 | 54 | 78 | 21 | 53 | 0.12 |
RT16-00 | 49 | 54 | 78. 5 | 29 | 57 | 0.16 |
RT16-1 | 67 | 72 | 136 | 48 | 62 | 0. 44 |
RT16-2 | 67 | 72 | 150 | 59 | 73 | 0. 66 |
RT16-3 | 67 | 72 | 150 | 67 | 85 | 0. 84 |
RT16-4 | 79 | 87 | 200 | 88 |
114 |
2. 03 |
5. Installation, use and maintenance of fuse
The fuse shall be installed indoors or in a cabinet that will not be affected by rain and snow, and shall not be exposed and installed in a place easy to touch.When installing the fuse, ensure that the electrical clearance is greater than 8 mm and the creepage distance is greater than 10 mm.In the circuit, the cross-sectional area of the connecting wire is recommended as the value in Table 4.
Model | Fuse rated current A | Sectional area of connecting wire 9 mm |
RT16-000 | 100 | 35 |
RT16-00 | 160 | 70 |
RT16-1 | 250 | 120 |
RT16-2 | 400 | 240 |
RT16-3 | 630 | 2X (40X5) |
RT16-4 | 1250 | 2X (60X5) |
When the fuse link is blown, a new fuse link with the same model, size and rated current as the original fuse link must be replaced instead of copper wire.
The replacement of fuse links shall be carried out by professionals using special fuse carriers.
When replacing the fuse link, it must be carried out under the condition of no load, preferably when the power supply is cut off. It is absolutely not allowed to use the fuse to cut off or connect the load when the switch is used. After replacing the fuse link, ensure that the contact between the fuse link and the base contact is in good contact.
When switching off the power supply and replacing the fuse link, please remove the dust and other dirt on the fuse base, especially the contact of the base, so that the fuse is in good working condition.
During operation, the indicator of fuse link shall be checked frequently so as to discover the single-phase or missing phase operation in time.
6.Transportation and storage of fuse
The fuse shall be protected from rain and snow during transportation and storage. The free drop height of the whole box fuse shall not be greater than 250mm.
Fuses shall be stored in a place with air circulation and dry environment, and the stacking height shall not exceed six layers.
7.Unpacking and inspection of fuse
After unpacking, first check whether the nameplate of the fuse is consistent with the packing list and the mark on the packing box, then check whether the fastener on the fuse base or fuse link is loose or falling o比 check whether the porcelain tube of the fuse link is cracked or cracked, check whether the quartz sand in the fuse block is leaking out, and check whether the fuse is soaked or attacked by water. If the above conditions are found, the fuse cannot be put into use, and the manufacturer shall be contacted in time.
The fuse box shall contain product certificate, packing list and operation instruction.
8. Ordering instructions
When ordering fuses, the model, specification, quantity and current grade of corresponding fuse links shall be indicated. The fuse base and fuse link can be ordered separately.
For fuses of special specifications and current levels, the manufacturer shall be consulted when ordering.
Product detail pictures:
Related Product Guide:
Gaining purchaser gratification is our company's aim eternally. We're going to make great initiatives to create new and top-quality products, satisfy your exclusive prerequisites and supply you with pre-sale, on-sale and after-sale solutions for ODM Extension Sockets Suppliers – Supply China Nt-500 Liquid Nitrogen Generators Nitrogen Gas Generator Machine Filling Machine Nitrogen – Jonchn , The product will supply to all over the world, such as: Madrid, Costa Rica, Estonia, We welcome an opportunity to do business with you and hope to have pleasure in attaching further details of our products. Excellent quality, competitive price, punctual delivery and dependable service can be guaranteed. For further inquires please do not hesitate to contact us.
By Myra from Korea - 2017.06.19 13:51
It can be said that this is a best producer we encountered in China in this industry, we feel lucky to work with so excellent manufacturer.
By Ingrid from Salt Lake City - 2017.09.28 18:29