ODM Avr Voltage Regulator Factory – ZC8000 Industrial Frequency Series – Jonchn Detail:
Product Features
- 1.Wide range of input voltage
2. Indicator light and LCD interface design in a friendly way
3. Micro-processor control, auto diagnosis, battery auto test
4. Pure on-line static bypass, strong overload and failure protection
5. RS232 and SNMP webmaster with remote monitoring and control function
6. Smart temperature control fan with long life service and low noise
7. More than 20 hours for MTBF, 20 minutes for MTTR
Technical Parameters
Technical parameters | |||||||||||
Model |
ZC8010 |
ZC8015 |
ZC8020 |
ZC8030 |
ZC8040 |
ZC8050 |
|||||
Output capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
50KVA |
|||||
Input |
voltage |
380VAC±20% (3Φ +4W ) |
|||||||||
frequency |
50Hz±10% /60Hz±10% |
||||||||||
Output |
voltage |
220VAC(±1%) |
|||||||||
frequency |
50Hz±0.05%/60Hz±0.05% free oscillation |
||||||||||
distortion |
Line load THD<3%; non-line load THD<5% |
||||||||||
waveform |
Pure sine wave |
||||||||||
peak factor |
3.1 |
||||||||||
power factor |
0.8-1 lag |
||||||||||
efficiency |
>92% |
||||||||||
overload ability |
<125% switch to bypass and recover aotomatically after 5min;<125%-150% switch to bypass and recover aotomatically after 30s | ||||||||||
transient response |
full load ±4% |
||||||||||
battery |
type |
Valve control type lead-acid battery |
|||||||||
DC voltage |
192/384VDC |
384VDC |
|||||||||
standard type |
12V/16/32 |
12V*32 |
|||||||||
Switch time |
bypass to inverter |
0ms |
|||||||||
inverter to bypass |
<2ms |
||||||||||
protection |
battery |
Non-fuse breaker |
|||||||||
short circuit |
Cut off inverter and bypass output at the same time |
||||||||||
over-temperature |
> 85℃ auto switch to bypass output |
||||||||||
EMI |
EN50091-2 |
||||||||||
Display |
LCD |
input voltage, output voltage, current, frequency, battery voltage, load %, UPS status, temperature., etc. | |||||||||
LED |
electric supply/bypass/inverter/battery/overload/failure |
||||||||||
Alarm sound |
battery low voltage |
Buzzing every second until shutdown, battery LED flashes every 2s |
|||||||||
UPS overload |
Continuous sound |
||||||||||
UPS failure |
Continuous sound |
||||||||||
AC failure |
Continuous sound every 4 seconds |
||||||||||
Working environment |
temperature |
0℃-40℃ |
|||||||||
humidity |
≤95%(no frost) |
||||||||||
noise (within 1M) |
<58db |
||||||||||
Weight |
|
180KG |
223KG |
239KG |
309KG |
355KG |
550KG |
||||
Dimension |
|
680*510*1130 |
195*455*330 |
1040*560*1410 |
Product detail pictures:

Related Product Guide:
The really abundant projects management experiences and 1 to just one provider model make the high importance of business enterprise communication and our easy understanding of your expectations for ODM Avr Voltage Regulator Factory – ZC8000 Industrial Frequency Series – Jonchn , The product will supply to all over the world, such as: Dominica, Bogota, Angola, We only supply quality products and we believe this is the only way to keep business continue. We can supply custom service too such as Logo, custom size, or custom products etc that can according to customer's requirement.

The company's products can meet our diverse needs, and the price is cheap, the most important is that the quality is also very nice.
