High frequency medium type series

The company’s UPS power supply is specially designed for the power system, using chip control, is a conversion device that converts the electricity of the city and the battery into uninterrupted, purified AC power, which is used to provide a continuous AC power supply for computers and other electrical equipment in case of power instability and power outage. It can also prevent various distortions of power grid, such as power supply voltage drop, surge voltage, peak voltage and broadcast frequency interference.

Read More>>


Product Detail

Product Tags

Product Features

Pure sine wave output

Extra wide input voltage

Indicator light with friendly LCD interface design

Full microprocessor control, self-diagnosis, battery automatic testing

Pure on-line static bypass, strong overload and fault protection intelligence

RS232 and SNMP webmaster providers remote monitoring function

MTBF reaches over 2 billion hours, MTTR reaches 20 minutes

Technical Parameters

Technical parameters

Model

ZC9006

ZC9010

ZC9015

ZC9020 ZC9030 ZC9030S

Output capacity

6KVA

10KVA

15KVA

20KVA

30KVA

30KVA

Input

voltage

110-300VAC (I-N)

 

frequency

50Hz±10% /60Hz±10%

Output

voltage

220VAC(±2%)

 

frequency

50Hz/60Hz±0.5% battery type

 

distortion

Line load THD<3%; non-line load THD<5%

 

peak factor

3.1(suitable for rectifier load)

 

power factor

0.8-1 lag

 

efficiency

≥0.88

 

overload ability

<130% switch to bypass and recover aotomatically after 30s;

<130%-150% switch to bypass and recover aotomatically after 20s

 

transient response

full load ±4%

battery

type

Valve control type lead-acid battery

 

DC voltage

192VDC

192VDC*2

 

standard type

12V/7AH (16)

12V/9AH*16*2

12V/9AH *16*2

Switch time

bypass to inverter

0ms

 

inverter to bypass

<2ms

protection

battery

Non-fuse breaker

 

short circuit

Cut off inverter and bypass output at the same time

 

over-temperature

Auto switch to bypass output when over temperature

 

EMI

100Hz-100KHz,40dB/100k-1000MHz,70dB

Display

LCD

input voltage, output voltage, current, frequency, battery voltage, load %, UPS status, temperature., etc.
 

LED

electric supply/bypass/inverter/battery/overload/failure

Alarm sound

battery low voltage

Buzzing every second until shutdown, battery LED flashes every 2s

 

UPS overload

Continuous sound

 

UPS failure

Continuous sound

 

AC failure

Continuous sound every 2 second until 90s

Working environment

temperature

0℃-40℃

 

humidity

≤95%(no frost)

 

noise (within 1M)

<58db

Weight

 

28kg

(standard type 73kg)

40kg

(standard type 143kg)

64kg

 

Dimension

 

592*250*576

592*250*576

(815*250*826 for standard stype)

397*145*220

 


  • Previous:
  • Next: