6-10kV Ring Main Unit, HXGN- 12

Read More>>


Product Detail

Product Tags

Environmental Conditions

◆ Altitude: lower than 1000 m; ◆ Ambient temperature: up to +40°C, greater than -25°C; ◆ Relative humidity: daily average ≤ 95%, monthly average ≤ 90% (+25°C); ◆ Areas without risks of fire, explosion, pollution, chemical corrosion and severe vibration;

Technical Parameters

Item Unit Parameter
Rated voltageMaximum working voltage KV 10/ 12
Rated current A 630
Busbar current Incoming cable A 630
Outgoing cable 125
Rated short time withstand current KA 20
Rated peak withstand current KA 50
Rated closed-loop breaking current KA 50
Rated mainly active load-breaking current A 630
Rated cable-charging current KA 20
Power frequency withstand voltage (1 min) KV 42
Rated lightening impulse withstand voltage KV 75
Mechanical endurance Vacuum load break switch times 10000
Dimension (W×D×H) mm 850×900×2000
Weight kg 200 ~ 300kg